Campus "Science City" stores heat in the ground

Building has been taking place for several weeks behind the HCL chemistry building on the Science City Campus, but downwards for once, not upwards. The first two ground heat storage fields for a sustainable heat supply network on the campus are currently being constructed here and under the new Life Science Platform (HPL) building in the north-eastern part of the campus.

There are 100 ground probes – plastic pipes 200 metres long – at the HPL and 130 behind the HCI. The pipes are sunk into the ground at five metre intervals, then connected to the building’s supply network. The plan is for 800 of these pipes to be located underneath and alongside the Science City buildings by 2020, which, together with other structural measures, will enable energy to be managed on the campus with almost no CO2 emissions, as stipulated by the ETH Zurich Energy Concept.

Like a big heat-exchanger

The building work stems from a decision made in 2006 by the then Vice-President for Planning and Logistics, Gerhard Schmitt. In the context of the impending renovation of the central heating system, he decided in favour of a pioneering project: the plan is for low-grade energy, known as anergy, to be stored in the ground via a large ground storage system, and subsequently reused. Cooling appliances or computer servers, as well as every student and employee, release heat into their surroundings. In the summer this heat needs to be removed by fans and coolers, otherwise the temperature in the auditoriums and offices would be unbearable. Until now most of this waste heat was discharged into the surrounding air, thus being lost to further use. In future it will be stored in the ground via ground storage probes operating like a large heat-exchanger.

Via circulating water system, the waste heat is put into storage in the cool ground, whose temperature ranges from 8 to 18°C. In winter the heat is pumped up again through the same circulation system and used to heat the building. Since the temperature range of 8 to 18°C is insufficient for this, the heat is “upgraded” to 30 to 35°C using several electrically-driven heat pumps. The system is decentralised: each building is equipped with a computer that controls precisely how much heat is needed to heat it.

Heat can be tapped off via the water circulation system from each of the storage units, nine of which will be installed by 2020. The target is for only one twelfth of the total energy for heating and cooling to be generated by electricity, i.e. high-value energy (exergy). The remainder will be extracted from the managed ground. The potential is enormous: although the ground’s heat capacity, around 1.0 kJ/kgK, is about one quarter of that of water, the gigantic volume of the ground storage compensates for this disadvantage. The engineers want to make four million cubic metres of ground usable on the Hönggerberg Campus. A density of 2500 kilograms per cubic metre and a 5 Kelvin temperature difference between charging and discharging yields a total capacity of 13 to 15 gigawatt-hours, corresponding to the energy content of around 1500 tons of petroleum.

Networking more important than insulation

The possibility of heat storage in the subsoil has far-reaching consequences for building design and running costs. Project Manager Thomas Gautschi from engineering consultants Amstein and Walthert Engineering describes it in a nutshell: “Don’t insulate like idiots, network well instead.” At Science City the main emphasis is no longer on ensuring the thickest possible insulation against heat losses, as in building standards such as Minergie P for example. Instead about the focus is on delaying the flow of heat and making the excess heat in summer usable for heating in winter.

With enough ground probes, high-efficiency insulation is unnecessary, and may even be a counter-productive. In fact, the ground storage can only absorb waste heat in summer if it is “emptied” during the winter; i.e. the earth is cooled back down to its original temperature. This opens up new prospects for building developers, especially for renovations: by networking buildings they gain more freedom in dealing with the existing building shells. Areas with numerous single buildings in particular, such as the Science City Campus, harbour a far higher potential for efficiency as a total networked system than as the sum of the individual structures.

Easy and economical

The ground storage system is also financially attractive. Hansjürg Leibundgut is Professor of Building Services at ETH Zurich and adviser to the project. He is convinced that “It will be very beneficial to ETH Zurich.” A façade renovation of a medium-sized building on the campus would cost about 15 million Swiss francs, a simpler re-glazing for lower heat losses five million. On the other hand, the ground storage currently installed under the HPL costs only 1.5 million Swiss francs. Moreover, upgrading the stored waste heat through a heat pump is cheaper than heating oil, and ground storage can hedge against fluctuations in the price of petroleum and, to a certain extent, electricity as well.

“There are many benefits, the system is relatively simple – it is surprising no-one thought of it sooner,” says Gautschi. The fact that there is still a lack of years of experience in dealing with ground probe boreholes is certainly one reason. They first came into existence in Switzerland 25 years ago. However, Leibundgut is convinced that ground storage will become accepted in Switzerland on a large scale in the future: “One day we will use the whole of Switzerland as a big heat store. A connection to a heat supply through the ground will then be taken for granted just like a connection to the drains or access to transport.”

Onto the network in 2011

First of all, however, the system must prove itself. There are, as yet, no reference projects. The plan is for the two heat storages at the HPL and behind the HCI to be connected to the network in mid-2011, followed by all nine storage units with a total of 800 probes by 2020. By then, however, ETH Zurich will probably no longer be the only site relying on heat storage in the ground. In fact, Gautschi is already planning comparable network systems for other clients in Zurich.

Media Contact

Claudia Naegeli idw

More Information:

http://www.ethz.ch

All latest news from the category: Power and Electrical Engineering

This topic covers issues related to energy generation, conversion, transportation and consumption and how the industry is addressing the challenge of energy efficiency in general.

innovations-report provides in-depth and informative reports and articles on subjects ranging from wind energy, fuel cell technology, solar energy, geothermal energy, petroleum, gas, nuclear engineering, alternative energy and energy efficiency to fusion, hydrogen and superconductor technologies.

Back to home

Comments (0)

Write a comment

Newest articles

Pinpointing hydrogen isotopes in titanium hydride nanofilms

Although it is the smallest and lightest atom, hydrogen can have a big impact by infiltrating other materials and affecting their properties, such as superconductivity and metal-insulator-transitions. Now, researchers from…

A new way of entangling light and sound

For a wide variety of emerging quantum technologies, such as secure quantum communications and quantum computing, quantum entanglement is a prerequisite. Scientists at the Max-Planck-Institute for the Science of Light…

Telescope for NASA’s Roman Mission complete, delivered to Goddard

NASA’s Nancy Grace Roman Space Telescope is one giant step closer to unlocking the mysteries of the universe. The mission has now received its final major delivery: the Optical Telescope…